中文

Home About News Technology Download Contact Information
Home > Product > 3AUP+ASC0Inquiries

3AUP+ASC

ComMax

Join Inquiry
feature of product |Product specifications |Outline drawing |Download
3AUP+ASC feature of product
model
3AUP+ASC
Max.Load Current
AC 1Φ, 3 wires or AC 1Φ, 2 wires : 100 ~ 320 V AC
3Φ, 4 wires + G (Star) : 480V/278V;415V / 240V ;400V/230V;380V/220V
AC 3Φ, 3 wires (Delta): 230V
Voltage Range
AC 100V~320V , 50 / 60 Hz
Suppressing Surges
Lightning Flash Surge ;power switching surges ; Switching Inrush Current
Electric Magnetic Pulse; Series Spark Surge; High Freq. Noise Suppression
Method to Handle Surge Energy
Surge Energy Transfer to Voltage, then release to later consecutive waves
Protection Mode
Line(L) –Neutral(N) ; Line(L) – Ground(G) ; Neutral(N) – Ground(G)
Residue Voltage
800Vp ±20%(at combination surge wave, 6KV/3KA)
Max Surge Immunity Test
Combination wave 1.2x50μs,10kV; 8x20μs,5kA, 5 times in 60 sec interval
Ground Resistance Requirement
None (Means, any resistance value is no influence to surge protection functions)
EMP/EFT Suppressed Rate
95%, at 4.5kV in 5x50ns EFT(Elec. Fast Transient/ Burst) waveform
Compliance standards
ANSI C62.41, cat. C,high exposure, IEC 61643-1, ANSI C37.90.1
IEC 61000-4-4(X-level,4.5KV), IEC 61000-4-5 (X-level,10KV)
Dimension & Weight
AUP: 81L x 43.5W x 42H , 200g ; ASC: 98L x 43.5W x 58H, 150g
Total per set : 98/81 L x 174 W x 58/42 H, mm / 750 g
Enclosure & Material
Industrial Fire Proof Plastic , IP66 / DIN rail and/or screw fixation
Operation temp. / Rel. Humidity
-20°C ~ 85°C / 35% ~ 95% RH (no condensing)

ComMax_SSPD_3AUP+ASC Datasheet
2020-03-27

Download

0.24MB

Back List